Product description
Aquacon® cartridges are constructed to remove dirt and water from hydrocarbon and other oils. The outer media layer filters out silt, rust and other particulate contaminants. The inner layers absorb water and chemically bond it so that no water will release downstream.When the Aquacon Cartridge reaches its water holding limit, the media swells shut and the differential pressure rapidly increases. This signals the operator that the cartridge must be changed.
Benefits:
Removes free and emulsified water to less than 2 ppm
Differential pressure increase alerts operator to change cartridges
Effectively filters silt and other particulates
No media migration or “linting”
Easy to install and remove
Does not affect oil additives
Fits standard filter housings
Technical Information:
Maximum operating temperature is 250°F (121.1°C).
Aquacon Cartridges will shut off flow when loaded with water or dirt.
Appropriate precautions should be taken in critical applications where oil flow must be maintained.
With some lube and hydraulic oils all of the water may not be removed in one pass, and extra passes will be required for total removal.
Water capacity for the AC-718 cartridges ranges from 2 to 4 quarts.
Applications:
Gasoline
Hydraulic Oil
Kerosene
Turbine Lube Oil
Diesel Fuel
Quench Oil
Insulating Oil
Synthetic Oil
Biodiesel
Phosphate Ester Oil
WARNING: Absorbent-type monitor cartridges will not remove water from fuel containing alcohol-blending agents (commonly called gasohol). For removal of solids, please use Velcon particle removal filters specifically made for gasohol. Consult your Parker representative.
The AC-718P3, AC-7181/2 and AC-7361/2 are increased surface area / reduced water capacity cartridges specifically designed for circuit breaker oil.